GGU-UNDERPIN: Analysis to EC 2/DIN 1045-1¶
The following verification is required to EC 2/DIN 1045-1:
NR,d = - (b · h · fm,d · )
where
= 1.14 (1-2etot/h) - 0.02 l0/h
and
0 ≤
≤ 1-2etot/h
Where:
NR,d = design value of the acceptable longitudinal force;
b = width of section;
h = thickness of section;
f m,d = design value of concrete compressive strength
= coefficient for considering the second order theory effects on the bearing capacity of compression members of unreinforced concrete in immovably braced structures;
etot = total eccentricity = e0 + ea + e
e0 = load eccentricity according to first order theory, where necessary taking the actions from adjoining floors into consideration (e.g. bending moments as a result of fixity, transferred from a slab to the wall), as well as the horizontal actions of wind ea, and the additional unintentional eccentricity as a result of geometric imperfections. If more precise data is not available, ea may be assumed at = 0.5 l0/200.
= eccentricity resulting from creep; generally, the e component can be disregarded.
Eccentricity limit¶
GGU-UNDERPIN only carries out the verification as long as the load eccentricity in the concrete section does not exceed 0.3 · b(concrete):
e(concrete) ≤ 0.3 · b(concrete)
If the eccentricity is larger, the coefficient is not calculated with the formula above but set to 0. The resistance Vr is then 0 and the degree of utilisation µ = 999.999: the verification is not satisfied at this depth. A hand calculation using the formula yields a value greater than 0 in this case and therefore differs from the program result.
The printout states this limit, marked with (*), in the header of the verification. Rows in which it applies are marked with (*) as well (from version 10.2).