GGU-UNDERPIN: Analysis to EC 2/DIN 1045-1
The following verification is required to EC 2/DIN 1045-1:
NR,d = - (b · h · fm,d · )
where
and
0 ≤
Where:
NR,d = design value of the acceptable longitudinal force;
b = width of section;
h = thickness of section;
f m,d = design value of concrete compressive strength
etot = total eccentricity = e0 + ea + e
e0 = load eccentricity according to first order theory, where necessary taking the actions from adjoining floors into consideration (e.g. bending moments as a result of fixity, transferred from a slab to the wall), as well as the horizontal actions of wind ea, and the additional unintentional eccentricity as a result of geometric imperfections. If more precise data is not available, ea may be assumed at = 0.5 l0/200.